Most motor protection is built on current. It is easy to measure and every motor starter already has an overload relay. But for many of the faults that cost plants the most, such as a pump running dry, a lightly loaded conveyor jamming or an agitator losing a blade, current is the wrong signal. True motor power, measured in kW, is the right one. This article explains why, and what it means in practice.
Current, in amps, measures how much electricity flows into the motor. True power, in kW, measures how much of that electricity is actually doing work. For a three-phase motor:
Power (W) = voltage × current × power factor × 1.73
The power factor is the key term. On an induction motor it reflects how much of the current is magnetising the motor rather than driving the load. A lightly loaded motor can have a power factor as low as 0.1; at full load it is typically around 0.9.
When a motor is lightly loaded, most of its current is magnetising current, which hardly depends on the load. As the load increases from zero, the power factor improves quickly while the current stays almost flat. On a typical motor, the current reading changes very little until the load reaches about half of full load.
Power behaves differently. Because it includes the power factor, it rises in a straight line with the load, with the same sensitivity at 10% load as at 90%. On a centrifugal pump, low flow means low power and high flow means high power, so the power reading tells you what is happening to the fluid.
Two real examples make the point. In a chlorine plant, motor current was not sensitive enough to detect a detached impeller on mercury pumps running below half load; power sensors with a low trip point did. On an ice cream mixer, power rose 15% over the batch while current rose only 5%, giving three times the signal to detect the end point.
Load Controls sensors measure current and voltage and calculate true power continuously. They install in the motor control cabinet, with nothing in the pipework or the process. The PMP-25 adds two trip points and a kW display for pump protection; the Universal Power Cell provides 4–20 mA and 0–10 V signals and works on variable frequency drives thanks to Hall effect sensing; fast response controls trip in 25 milliseconds for jams. See our technology page for the full explanation and the product range to choose a sensor.
Is a power sensor more expensive than a current relay?
It usually costs more than a basic current relay, but it detects the light-load faults a current relay cannot, which are often the ones that destroy pumps, seals and gearboxes.
Can I use an existing current transformer?
Many Load Controls sensors are self-contained and need no current transformer. For larger motors, controls such as the PMP-25 work with an external current transformer, which we specify.
Does power monitoring work on motors with variable frequency drives?
Yes, with a Universal Power Cell installed on the drive output. Standard sensors designed for mains supply can misread a drive's distorted waveform.
Which sensor should I start with?
For pumps, the PMP-25. For a power signal into a PLC or DCS, the Universal Power Cell. For jams, the fast response controls. Tell us the application and motor size and we will recommend the right model.
Need help choosing a sensor?
Tell us your application and motor size, and we will recommend the right Load Controls product and send a quotation.