Water and wastewater plants run pumps, collectors and mixers around the clock, often at remote or unattended sites. Load Controls power sensors protect that equipment from the motor control centre, away from the wet end, and give operators an energy and condition signal for every motor.
Collectors and clarifier drives are slow, heavily geared and expensive to repair. A jam from heavy sludge or debris can break a chain or flight long before a thermal overload reacts. In one case study, a large US water utility could not mount sensors on its sludge collector motors and found current sensing too insensitive. It fitted a PFR-1750 power control to each motor's supply wiring, with a lower set point to warn of rising load and a higher one to stop the motor on a jam, an electronic shear pin with no mechanical parts.
On drive-fed pumps the Universal Power Cell measures on the drive output. See monitoring and protecting pumps.
Industry analysts quoted by Load Controls estimate that up to 70% of pumps are oversized, many by more than 20%. Measured power shows how much of each motor's rating is actually used. As an example, replacing a 22 kW motor with a 15 kW one on a duty that suits it saves about 7.5 kW; at 40 hours a week that is roughly 15,500 kWh a year, and four times more on a continuous duty.
Mixer power confirms that anoxic and storage tanks are being mixed and reveals a lost blade; blower power tracks aeration load; centrifuge and screen power shows overloads and blockages. All can be logged by asset for energy reporting.
Further reading: Electronic shear pins, Energy efficiency and ISO 50001, Why measure power, not amps
Can I protect a sludge collector without a sensor on the motor?
Yes. The control measures power on the motor supply cables in the motor control centre, so nothing is mounted on the collector or the motor.
Why not use a current relay?
Collector and pump faults often change the load by only a small amount, especially at light load where current barely moves. Power changes in proportion to the work, so it detects these faults reliably.
Can the sensors send data to our SCADA system?
Yes. The Universal Power Cell provides 4–20 mA and 0–10 V outputs, the UPC-MB communicates over Modbus, and the PMP-25 has a 4–20 mA output alongside its relays.
Do they work on pumps with variable frequency drives?
Yes. The Universal Power Cell is installed on the drive output and measures true power across the speed range.

Tell us the application, motor size and drive type. We will recommend a model and send you a quotation. 12-month warranty and support from our team in France.